< Return to Video

How Are Building Occupant Loads Determined? | ARTiculations

  • 0:00 - 0:05
    Have you ever seen one of those signs indicating
    the occupant capacity of a room and thought,
  • 0:05 - 0:07
    how exactly do they get that number?
  • 0:07 - 0:11
    If you thought it was how many people could
    be physically packed into the room shoulder
  • 0:11 - 0:14
    to shoulder then, no that’s most likely
    not it.
  • 0:14 - 0:19
    Occupant loads are, for the most part, determined
    by: means of egress, which basically means
  • 0:19 - 0:24
    the design of exiting components throughout
    the space, as well as the number of available
  • 0:24 - 0:27
    sanitary fixtures such as toilets and lavatories.
  • 0:27 - 0:31
    So how are these components designed to meet
    the intended occupant load?
  • 0:34 - 0:39
    Egress is arguably one of the most important
    aspects of architectural and interior design.
  • 0:39 - 0:44
    The exiting requirements for proper and safe
    evacuation depends largely on
  • 0:44 - 0:46
    what the space is being used for.
  • 0:46 - 0:51
    For example a movie theatre will usually hold
    more people compared to a typical office of
  • 0:51 - 0:56
    the same size, and a storage room carrying
    flammable liquids is more dangerous than a
  • 0:56 - 0:57
    typical residential dwelling.
  • 0:57 - 1:00
    Building codes also differ depending on where
    you are.
  • 1:00 - 1:06
    Here in North America, most states, provinces
    and municipalities will adopt “model building
  • 1:06 - 1:10
    codes,” such as the International Building
    Code, or the National Building Code of Canada.
  • 1:10 - 1:14
    For this video I will refer mostly to the
    IBC.
  • 1:14 - 1:16
    In order to determine egress provisions.
  • 1:16 - 1:19
    We need to figure out how many people are
    expected to use a space.
  • 1:19 - 1:23
    In a space that only contains fixed seats,
    like a movie theatre,
  • 1:23 - 1:25
    it’s pretty straight forward to figure that out.
  • 1:25 - 1:28
    It can be done by counting the number of seats.
  • 1:28 - 1:30
    But what about spaces without fixed seating?
  • 1:30 - 1:36
    Well, another method is to use the “occupant
    load factor” table provided in the building code.
  • 1:36 - 1:42
    For example, the load factor of an exhibit
    gallery or museum is 30 sqft/occupant.
  • 1:42 - 1:47
    So in a 3000 sqft room the occupant load for
    an art gallery would be 100.
  • 1:47 - 1:52
    In Business Areas, such an office, the load
    factor is 150 sqft/occupant.
  • 1:52 - 1:56
    So in the same space the occupant load for
    an office would be 20.
  • 1:56 - 2:01
    The load factor table, however, does not restrict
    the space from having more occupants.
  • 2:01 - 2:07
    The 3,000 sqft gallery can be designed for
    more than 100 people, as long as the requirements
  • 2:07 - 2:12
    for egress, life safety, sanitary fixtures
    and other code mandates are satisfied.
  • 2:12 - 2:16
    The more difficult thing to do is designing
    the space for less occupants than what’s
  • 2:16 - 2:18
    specified by the load table.
  • 2:18 - 2:24
    So if you’re trying to argue what this 3000
    sqft gallery will only be used by a maximum
  • 2:24 - 2:29
    of 25 people at any given time, then you need
    to make a good case to the local building
  • 2:29 - 2:31
    official and they would have to approve it.
  • 2:31 - 2:33
    So let’s talk exits.
  • 2:33 - 2:35
    Or more accurately - means of egress.
  • 2:35 - 2:37
    What exactly is a means of egress?
  • 2:37 - 2:43
    Well the IBC defines it as “a continuous
    and unobstructed path of vertical and horizontal
  • 2:43 - 2:49
    egress travel from any occupied portion of
    a building or structure to a public way.”
  • 2:49 - 2:53
    The reason we talk about it in this way is
    because exiting a building is not a one-step
  • 2:53 - 2:58
    event, it’s a process that involves multiple
    exiting components.
  • 2:58 - 3:02
    So, pretty obvious - every space needs at
    least one means of egress.
  • 3:02 - 3:07
    But two or more means of egress are required
    if the space exceeds a certain occupant load
  • 3:07 - 3:10
    under certain occupancy classifications.
  • 3:10 - 3:15
    Occupancy classifications are formal designations
    for the primary purpose of the building or
  • 3:15 - 3:16
    portion of building.
  • 3:16 - 3:20
    Since Art Galleries normally fall under the
    Assembly occupancy, we would look under the
  • 3:20 - 3:26
    requirements for Occupancy A, which indicates
    that if the space only has one means of egress,
  • 3:26 - 3:29
    the occupant load cannot exceed 49.
  • 3:29 - 3:33
    In our case of 100 occupants, we would have
    to provide two means of egress.
  • 3:33 - 3:38
    Exits, or access to exits, also have to be
    positioned and spaced accordingly.
  • 3:38 - 3:42
    Because, say there is a fire blocking the
    path to one doorway, there needs to be an
  • 3:42 - 3:44
    alternative way to get out.
  • 3:44 - 3:48
    You can’t just have two doors next to each
    other and call that two exits.
  • 3:48 - 3:50
    They have to be certain distances apart.
  • 3:50 - 3:55
    And the distances are based on ratios and
    formulas outlined by the code which may vary
  • 3:55 - 3:58
    depending on if the building is sprinklered
    or not.
  • 3:58 - 4:02
    The means of egress also have to be large
    enough to handle the occupant load.
  • 4:02 - 4:07
    For example, doorways and corridors along
    a means of egress must have a clear headroom
  • 4:07 - 4:14
    of 80” high, have a minimum clear width
    of 32” for doors, 36” for corridors
  • 4:14 - 4:22
    44" for corridors serving an occupant load of
    50 or more, or 0.2” multiplied by the occupant load,
  • 4:22 - 4:23
    whichever is more.
  • 4:23 - 4:28
    These width capacities may be reduced in certain
    occupancies if the space is equipped with
  • 4:28 - 4:30
    an automatic sprinkler system.
  • 4:30 - 4:33
    Going back to our art gallery that require
    two means of egress.
  • 4:33 - 4:36
    Let’s say they are exit access doorways.
  • 4:36 - 4:40
    Since 0.2” x 100 is only 20”.
  • 4:40 - 4:45
    In this case, both doors have to be at least
    32” wide each.
  • 4:45 - 4:49
    This is not necessarily the size of the door
    though, it’s actually the clear opening
  • 4:49 - 4:54
    between any protruding hardware when the door
    is opened at 90 degrees.
  • 4:54 - 4:59
    So often a 36” door needs to be used to
    achieve a 32” opening.
  • 4:59 - 5:02
    Let’s take a look at an example with a higher
    occupant load.
  • 5:02 - 5:05
    For instance a community meeting room with
    loose seating.
  • 5:05 - 5:10
    This usage, as per the load factor table is
    listed as 7 sqft/occupant.
  • 5:10 - 5:14
    So in our 3000 sqft room we could expect 429
    people.
  • 5:14 - 5:19
    Which when multiplied by 0.2” would equal
    85.8”.
  • 5:19 - 5:24
    Since we definitely need at least two exits
    or exit access doorways, one way to achieve
  • 5:24 - 5:29
    this is by having two doors, each having a
    clear width of a least 42.9”.
  • 5:29 - 5:33
    In High Hazard occupancies, and in all other
    occupancies where the occupant load of the
  • 5:33 - 5:39
    space is 50 or more, the door also must swing
    in the direction of exit travel.
  • 5:39 - 5:44
    Occupant load above certain capacities may
    also trigger life safety and fire protection
  • 5:44 - 5:48
    requirements, such as requirements for automatic
    sprinklers and fire alarm systems.
  • 5:48 - 5:53
    But while life safety and means of egress
    are very important building components, so
  • 5:53 - 5:56
    are personal hygiene and access to toilets.
  • 5:56 - 6:01
    Thus building codes mandate a minimum number
    of toilets, lavatories, drinking fountains,
  • 6:01 - 6:05
    service sinks, and sometimes also bathtubs
    and showers.
  • 6:05 - 6:10
    As per IBC, In the office area, we would need
    to provide 1 water closet for every 25 persons
  • 6:10 - 6:13
    of each sex for the first 50 people.
  • 6:13 - 6:18
    Since we only have 20 people, that’s 10
    males and 10 females, we could provide
  • 6:18 - 6:19
    one restroom per sex.
  • 6:19 - 6:23
    However, there is an exception in the code
    where you do not need to provide a separate
  • 6:23 - 6:28
    facility for each sex in business occupancies
    of 25 or less.
  • 6:28 - 6:32
    So in this case, providing one restroom total
    is acceptable.
  • 6:32 - 6:36
    In addition, based on our occupant load, a
    minimum of one lavatory, one drinking fountain
  • 6:36 - 6:39
    and one service sink are also required.
  • 6:39 - 6:44
    In the community meeting room of 429 people,
    the requirement is one water closet for every
  • 6:44 - 6:49
    65 females and 1 for every 125 males.
  • 6:49 - 6:53
    Since we have about 215 of each sex, this
    means we need four water closets for women
  • 6:53 - 6:54
    and two for men.
  • 6:54 - 6:57
    In the female restroom this would be four
    toilets.
  • 6:57 - 7:01
    In the male restroom, up to half of toilets
    can be urinals.
  • 7:01 - 7:05
    In case you’re wondering why women get more
    toilets than men, this is due to the fact
  • 7:05 - 7:09
    that biologically it takes longer for women
    to use the restroom.
  • 7:09 - 7:14
    Additionally one lavatory is required for
    every 200 people of each sex, this means we
  • 7:14 - 7:16
    need two lavatories for both restrooms.
  • 7:16 - 7:20
    And, one drinking fountain and one service
    sink are also required.
  • 7:20 - 7:25
    Essentially, every built environment needs
    to be designed to allow its occupants to exit
  • 7:25 - 7:31
    safely in a timely manner in the event of
    an emergency, and provide adequate toilet
  • 7:31 - 7:34
    and personal hygiene facilities for its occupants.
  • 7:34 - 7:38
    While the examples I’ve given in this video
    are relatively simple, there are many more
  • 7:38 - 7:39
    complex requirements.
  • 7:39 - 7:44
    Plus, real world environments are generally
    not as straight forward, and often deal with
  • 7:44 - 7:48
    existing construction, mixed occupancies and
    municipal regulations.
  • 7:48 - 7:53
    Thus, most of the time, load calculations
    and code reviews must be carried out by
  • 7:53 - 7:56
    a licensed interior designer or architect.
  • 7:56 - 8:02
    I find that a lot of people perceive creative
    design to be dominated by form and aesthetics.
  • 8:02 - 8:07
    When in reality, form is often secondary to
    function, and design can be quite a constrained
  • 8:07 - 8:10
    exercise with a lot of limitations.
  • 8:10 - 8:15
    However, personally I think working with constrained
    parameters is even more interesting and,
  • 8:15 - 8:18
    as a matter of fact, requires even more creativity.
  • 8:18 - 8:19
    Thanks for watching.
  • 8:19 - 8:24
    This episode is a part of a series where I
    explore various aspects of
  • 8:24 - 8:26
    the interior design profession.
  • 8:26 - 8:29
    If you liked it, then you may enjoy some of
    these as well.
  • 8:29 - 8:30
    And please subscribe to keep watching.
  • 8:30 - 8:31
    Until next time! *snap!*
Title:
How Are Building Occupant Loads Determined? | ARTiculations
Description:

more » « less
Duration:
08:40

English subtitles

Revisions